WSG series intelligent temperature & humidity controllers
Summary&application:
WSG series intelligent temperature & humidity controllers are composed of two parts including display control instruments and sensors. The meter is extensively applied in electric power, building, petrifaction, agriculture and so on industries. It can take real-time measurement and fault alarm of the temperature & humidity of the measured environment. It can control the temperature & humidity of the measured environment within the specified range, to guarantee the safety and reliable operation of the devices by controlling external heaters and fans.
The meter conforms to country standard GB/T 13639《analog input digital indicators for industrial process measurement and control systems use》, JB/T 8386.1~2《analog input digital indicating controllers for industrial process measurement and control systems use》
1. Main functions and characteristics:
◆Adopting SCM data analysis control, analog and digital multiple filtering technique, it is characterized with high accuracy and strong anti-interference ability.
◆Digital tube display, small volume, complete function, beautiful appearance, button setting, easy operation, convenient installation and connection.
◆It has perfect self-checking and protection functions, displaying the indications when error occurs and closing the control.
◆It can monitor the temperature & humidity of the environment, with temperature rise/drop optional, cooling or dehumidifying through automatically starting the load to heat, to control the temperature & humidity of the environment within the required range.
2. Model composition and representative meanings:
3. Main technical performance and parameters:
Technical parameters | index | ||
Temperature control range | -20~70℃ | ||
Temperature control accuracy | ±2℃ | ||
Humidity control range | 0% RH ~99% RH | ||
Humidity control accuracy | ±5% RH | ||
Output specification | Relay contact switch output 240V AC/10A (for resistive load) | ||
Display mode | LED nixie tube display | ||
Working power supply | Range | AC220V±10%, 50/60Hz | |
Consumption | <5VA | ||
Safety |
withstand voltage | Input & auxiliary power supply | > 2kV 50Hz/1min |
Input & output | > 2kV 50Hz/1min | ||
Output &auxiliary power supply | > 2kV 50Hz/1min | ||
Insulation resistance | Auxiliary power supply, input, output terminal of the case>100MΩ | ||
Heatproof& Flaming retarding | Terminal base: 960℃, case of the meter: 650℃, time of operation: 30s | ||
Electromagnetic compatibility | Electrostatic discharge | ±8kV | |
Fast transient pulse group | ±1kV | ||
Operating environment | Temperature range | -20℃~70℃, non corrosive gas occasions |
4.External and installation size:
(Unit: mm)
Model | Panel size | Shell size | Cutting size |
WSG series | 50×50 | 45×45×86 | 46×46 |