Temperature Controller

Temperature Controller

XMT-4000 series digital temperature indicating regulators Summary&application: XMT-4000 series digital temperature indicating regulators has variety of advantages, such as high accuracy, easy installation, good reliability, strong anti-vibration and anti-interference ability, etc. With...

Product Details

XMT-4000 series digital temperature indicating regulators

Summary&application: 

XMT-4000 series digital temperature indicating regulators has variety of advantages, such as high accuracy, easy installation, good reliability, strong anti-vibration and anti-interference ability, etc. With various of external sizes and complete control mode, it can be widely applied into temperature measurement and automation control within -200℃to 1800℃ for those industries including plastic, rubber, packing, food machinery, metallurgy, refrigeration, chemical, medical treatment, etc.


1Main functions and characteristics:

◆High cost performance with accuracy of class one, adopting keyboard input settings.

◆Support same type of sensor with graduation freely switched, full range of measurement and automatic switching for resolution

◆The input adopts digital correction system, the built-in common thermocouple and hot-resistance non-linear correction table for accurate measurement.

◆The potentiometer regulation and time scale regulation can be freely switched, and the positive& negative effect can be set.

◆It has perfect self-checking and protection function. According to the nature of the error, it can automatically correct or timely propose and close output when errors occur. 

 

2. Model composition and representative meanings:

6.jpg


3. Input specification and measuring range:

Input type

Graduation

Measuring range

 

 

Thermocouple (TC)

K

-50~+1350℃

S

-50~+1750℃

R

-50~+1750℃

T

-200~+400℃

E

-50~+800℃

J

-50~+1000℃

B

0~+1800℃

N

-50~+1300℃

Hot resistance (RTD)

Cu50

-50~+150℃

Pt100

-200~+850℃

Resistance ®

30Ω~350Ω

 


4. Main technical performance and parameters:

Item

Type index

Basic error

±1.0%F·S±1 word

Sampling period

<0.3s

Regulation mode

≤±1.0%F·S ≤±0.5%F·S

Switch difference

Position regulation (positive/negative effect and switch difference can be set)
Time scale regulation(positive/negative effect and proportional band, null cycle and manual adjustment coefficient can be set)

Cold end compensation

The error is less than 2℃ within the range 0℃~40℃

Alarm mode

Have upper-limit alarm and lower-limit alarm, can realize single way alarm output, can freely choose resolute value alarm or

deviation alarm

Output specification

Relay contact switch output: 28VDC/5A, 250VAC/5A
Solid state relay drive voltage output: 12VDC/25mA

Work power supply

AC198V~242V, 50Hz/60Hz, consumption<5VA

Work environment

Temperature 0℃~50℃, the relative humidity no more than 85%

non-corrosiveness places


Note: 

F·S is the range of the meter. The meter with B  graduation thermocouple can measure within the range 0~+1800℃, but the basic error can not be guaranteed below 600℃.


5. External  and installation size:
(unit:mm)

Model

Panel size

Shell size

Cutting size

XMTA series

96×96

90×90×80

92×92

XMTE series

48×96

44×90×100

45×92

XMTB series

60×120

55×112×80

56×114

XMTG series

48×48

44×44×100

45×45

XMTD series

72×72

66×66×80

68×68

XMTH series

160×80

150×75×100

152×76